Engineering via SICAM WEB
364 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Category Parameter Meaning
PRE_(RED) Protocol element number
Priority_(RED) Priority 0 (lowest)…priority 14 (highest)
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
Redundancy return in-
formation message
Return_information_function_
(RED)
Redundancy state
Switchover runs at a global switchover
Keyswitch of the SCA-RS: system A active
Keyswitch of the SCA-RS: automatic
Keyswitch of the SCA-RS: system B active
Listening mode
BSE_(RED) Basic system element
PRE_(RED) Protocol element number
Selective data flow rout-
ing
PRE Protocol element number (0…3)
Station 0…99 = selective station
unused = single-point-PRE or multi-point-
PRE to all remote stations
Data_class
Data class 1
Data class 2
Periodical transfer Selection periodical level or no periodical
transfer
Event_data
Time_tag Transfer with or without time tag
Function_group
address-conversion 0 = yes, 1 = no
Change_sign_of_measured_
values
New_CASDU1 New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New_CASDU2 New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New_IOA1 New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New_IOA2 New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.