EasyManua.ls Logo

Siemens CP-8022

Siemens CP-8022
614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Components and Technical Data
158 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.3.4 AI-6310
5.7.3.4.1 Functions
Temperatures
t1
Acquisition of resistance thermometers via analog inputs of a SM-0571
Connection of the resistance thermometers: 2-, 3-, or 4-wire technique
Update every 400 ms
Settable measuring range
Temperaturwerte
Input range
Pt100: -50…+350°C / -58…+662°F / (80,31…229,67 )
Pt100: -100…+700°C / -148…+1292°F / (60,25…345,13 )
Ni100: -60…+250°C / -76…+482°F / (69,5…289,2 )
Resolution
Pt100: -50…+350°C 0.15°C / 0.28°F / (56 m)
Pt100: -100…+700°C 0.15°C / 0.28°F / (56 m)
Ni100: -60…+250°C 0.15°C / 0.28°F / (56 m)
Update grid
16 Hz <6,8 s
50 Hz < 5,6 s
60 Hz < 5,2 s
Resistance values
Input range 40…400
Resolution 56 m
Update grid
HW rev. ="--" HW rev. "-A"
16 Hz < 6,8 s 16 Hz < 1,68 s
50 Hz < 5,6 s 50 Hz < 1,44 s
60 Hz < 5,2 s 60 Hz < 1,36 s
Revision
Noise rejection
Automatic calibration
Calibration for 2-wire technique
Smoothing
Adaptation
Temperature value (°C, °F), conversion using implemented curves
Resistance ()
Change monitoring
Spontaneous transmission of changes

Table of Contents

Related product manuals