System Components and Technical Data
148 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.2.1 DI-8110, DI-8111, DI-8112, DI-8113
5.7.2.1.1 Functions
Single-point information
Acquisition with a resolution of 1 ms
t
Update every 10 ms
a
(in the cycle of the open-/closed-loop control function, if larger)
Revision
ta
Power monitoring
ta
Inversion
ta
Firmware filter
t
Bounce suppression
t
Determination of the cause of transmission
t
Spontaneous transmission of changes
t
Periodical transmission
a
Double-point information
Acquisition with a resolution of 1 ms
t
Update every 10 ms
a
(in the cycle of the open-/closed-loop control function, if larger)
Revision
ta
Power monitoring
ta
Inversion
ta
Firmware filter
t
Bounce suppression
t
Monitoring intermediate and faulty positions
t
Determination of the cause of transmission
t
Reporting switching operations in progress
t
Breaker tripping detection
t
Breaker tripping suppression during auto-reclose
t
Spontaneous transmission of changes
t
Periodical transmission
a
Integrated totals via count pulses
t1
Acquisition by firmware with a maximum count frequency of 20 Hz
Pulse length/pause >20 ms/>20 ms
Revision
Power monitoring
Inversion
Pulse counting
Counter value formation
Count pulse evaluation
Set counter
Formation of integrated totals
Counter request
Interval control
Frozen absolute value
Frozen relative value
Not power-fail safe
Integrated total transmission according to iec 60870-5-101
Spontaneous transmission

Table of Contents