System Components and Technical Data
150 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.2.3 AI-8310
5.7.2.3.1 Functions
Temperatures
t1
Connecting resistance thermometers: 2-, 3- or 4-wire technique
Settable measuring ranges
Temperature values
Input range
Pt100: -50…+350°C / -58…+662°F / (80.31…229.67 )
Pt100: -100…+700°C / -148…+1292°F / (60.25…345.13 )
Ni100: -60…+250°C / -76…+482°F / (69.5…289.2 )
Pt1000: -100…+700°C / -148…+1292°F / (602.5…3451.3 )
Resolution
Pt100: -50…+350°C 0.15°C / 0.28°F / (10 m)
Pt100: -100…+700°C 0.15°C / 0.28°F / (10 m)
Ni100: -60…+250°C 0.15°C / 0.28°F / (10 m)
Pt1000: -100…+700°C 0,15°C / 0,28°F / (100 m)
Response time
16 Hz < 1.2 s
50 Hz < 1.0 s
60 Hz < 0.9 s
Resistance values
Input range
40…400 , Resolution: 10 m
400…4000 , Resolution: 100 m
Response time
16 Hz < 1.2 s
50 Hz < 1.0 s
60 Hz < 0.9 s
Revision
Noise rejection
Calibration for 2-wire technique
Smoothing
Adaption
Temperature value (°C, °F), conversion using implemented curves
Resistance value ()
Change monitoring
Spontaneous transmission upon change