General Information
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 35
DC8-037-2.02, Edition 10.2017
1.2 Performance Characteristics
General features CP-8000 CP-8021 CP-8022
Maintenance-free, small compact device for mounting on DIN rail ü ü ü
Local operation via function keys and display (LCD) ü - -
Internal digital inputs for binary information acquisition 12 - -
Internal digital outputs for command output 8 - -
Expandable with external SICAM I/O Modules 6 8 8
Expandable with external SICAM TM I/O Modules 6 - -
Combined automation and telecontrol function ü ü ü
Freely programmable application programs according to
IEC 61131-3
ü ü ü
Communication
Ethernet interfaces 10/100Base-TX with parameter-settable proto-
cols according to IEC 60870-5-104, IEC 61850 Ed. 2 Client/Server,
DNP 3 TCP/IP Slave
2
1)
2
1)
2
1)
Serial interfaces with parameter-settable protocols according to
IEC 60870-5-101/-103, Modbus RTU, DNP 3 and others
2
2)
2
2)
3
2) 3)
Integrated GPRS modem - - ü
Engineering, diagnosis and test via SICAM TOOLBOX II
SICAM TOOLBOX II connection via LAN/WAN (“remote connec-
tion”)
Connection via proprietary TCP/IP protocol (one
SICAM TOOLBOX II session can be served at the same time)
ü ü ü
Integrated web server for the engineering, diagnosis and test via
web browser (application SICAM WEB)
Access to the web server with standard web browser via http(s)
ü ü ü
Engineering via SICAM Device Manager ü ü ü
Optional autoconfiguration via DHCP service ü ü ü
Optional dynamic IP settings via DHCP server ü ü ü
Integrated protocol SNMP ü ü ü
Time synchronization via SNTP server ü ü ü
Simplified maintenance operation by means of data storage on SD
card
ü ü ü
Optional authentication via RADIUS server ü ü ü
Secure password storage ü ü ü
Security
BDEW White Paper conformity and integrated crypto chip
IPSec
Security Logging
ü ü ü
Process signal status display via LCD ü - -
Function and error display via LED ü ü ü
1)
common or separate IP address configurable (2 MAC addresses reserved, see type label of the de-
vice)
2)
1x RS-232 and 1x RS-485
3)
1x selectable RS-232 or RS-485

Table of Contents