Ambient Conditions
86 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
4.4.8 Storage and Transport
Storage
Store the device in dry and clean rooms. The relative humidity must not lead to the formation
of either condensation water or ice.
For storage Siemens recommends that you maintain a limited temperature range of between
+10°C and +35°C, in order to prevent premature ageing of the electrolytic capacitors used.
For a longer storage period Siemens also recommends connecting the device to the supply
voltage once a year for 1 to 2 days, in order to form the electrolytic capacitors used. You
should proceed likewise before a planned use of the device.
Transport
The transport packaging of the devices can be re-used for forwarding. If other packaging is
used the observance of the transport requirements according to ISO 2248 must be ensured.
Storage packaging of the individual devices is not adequate for transport.