System Components and Technical Data
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 163
DC8-037-2.02, Edition 10.2017
5.7.3.9 AO-6380
5.7.3.9.1 Functions
Setpoint values by means of currents and voltages
Output via analog outputs of a SM-0572
ta
Output range settable with a resloution of
ta
12 bits + sign at ±20 mA/±10 V
Shrinking the range results in decreasing resolution
Application functions and procedures according to IEC 60870-5-101/104
ta
Formal check
Direct command
Select and execute command ("select/execute")
Adaptation
t
Linear (normalized, technologically scaled or short floating point)
t
Selectable behavior on communication failure and module failure
ta
(keep value, output substitute value)
Spontaneous transmission
t
or
Periodical transmission
a