Preparing the Engineering
282 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
7.8.2.9 Exceptions with Engineering via SICAM WEB
The parameter records in the SICAM TOOLBOX II and in the SICAM WEB are basically iden-
tical structured. However, for the engineering via SICAM WEB some simplifications exist,
hence the following functions are not supported or implemented in another manner:
HW configuration Master Module
The Master Module is automatically configured as soon as a SD card with the firmware
CPC80 has been installed.
System technique I/O Master Module
After the configuration of the I/O Master Module the I/O Modules must be configured in the
OPM II. With the engineering via SICAM WEB the I/O Modules are configured automati-
cally.
Process technique I/O Master Module
In contrast to the OPM II no images are applied, for each I/O Module an assignment page
and a parameter page exist.
In the assignment page the usage of the I/Os is defined (according to the assignment in
the SICAM TOOLBOX II).
In the setting page the previously configured I/Os are parameterized. There appear only
the parameters relevant for the defined usage.
Process technique protocol element
In contrast to the OPM II no images are applied, the process technique is provided as
spreadsheets (send detailed routing, receive detailed routing).
Loading firmware of protocol elements
Protocol elements can not be loaded slot-selectively. If for instance on PRE0 and on PRE1
the system element UMPST0 is configured, both are loaded.
Message simulation
The message simulation is not supported (inserting of arbitrary messages into the sys-
tem). However, there is the possibility of displaying current process values of the periphery
(binary information states, integrated totals, measured values) and to set process values
(commands, setpoint commands).
Data flow test
The data flow test is not supported (different log points, filters, etc.).
Revision interrogation
The current firmware revision of the Master Module is displayed in the header of the user
interface, the revisions of the additional system elements (protocol elements, I/O Master
Module) in the drop-down menu on the configuration page.
Application program
A graphical function diagram (FUD) creation is not possible, only an instruction list (IL) with
ASCII format can be loaded into the target device.
Test of the application program
Offline simulation of the application program is not possible. A simplified online test (state
display, forcing of a selectable signal) is available.