EasyManua.ls Logo

Siemens CP-8022

Siemens CP-8022
614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Components and Technical Data
108 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.5.4 BPPT0
5.5.4.1 Functions
Communication of a central station with a substation.
Serial communication protocol according to IEC60870-5-101
Balanced point-to-point transmission
Network configuration
Point-to-point configuration
Multiple point-to-point configuration
*)
Max. connections: 1
System or device (application function)
Controlled station
Controlling station
Physical layer / data flow control
Unbalanced interchange circuit accordingV.24/V.28 standard
Transmission medium (full duplex)
Byte Frame (8E1)
Data flow control Bit in receive direction
Interoperability
IEC60870-5-101 Ed.1
Interoperability according to the following document:
SICAM RTUs Interoperability IEC 60870-5-101/104 (DC0-013-2)
Acquisition of events (transmission of data ready to be sent)
General interrogation, outstation interrogation
Non Interruptible GI
Clock synchronization according IEC 60870-5-101
Clock synchronization with <TI:=103> clock synchronization command
Acquisition of transmission delay (primary station) used for correction of clock syn-
chronization with <TI:=106>
Acquisition of transmission delay (secondary station) used for correction of clock syn-
chronization with <TI:=106>
Command transmission
Set control location
Check control location
Transmission of integrated totals
File transfer
Optimized parameters for selected transmission facilities (modems)
Free definable parameters for transmission facility
Protocol element control and return information
Protocol element control
Send (general) interrogation command to all
Send (general) interrogation command to selective CASDU
Send (general) interrogation command for image GI to own Master Module
Set control location
Data filter in transmit direction ON/OFF“
Data filter in receive direction “ON/OFF
Activate/Deactivate interface
Activate/Deactivate interface + protocol functions

Table of Contents