SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 263
DC8-037-2.02, Edition 10.2017
7.7.2.2.1 Point-to-Point Connection via Serial Interface
The following steps are necessary:
Configure IP address for engineering PC
Connection setup via SICAM WEB
Configure IP Address for Engineering PC
For the parameter setting the IP addresses predefined in CP-8000/CP-802x are used. There-
by the web server of the target device assignes automatically the IP address 172.16.0.2 to
the engineering PC, if this is configured for the automatic acceptance of an IP address.
For the communication via the serial interface, a dial-up connection must be set up on the en-
gineering PC. You find the instruction thereto in Appendix D, Set Up Dial-Up Connection on
Engineering PC.
Connection via SICAM WEB
Start the web browser and enter the IP address of your target device (172.16.0.1) in the
address bar.
You find the further information in chapter 9, Engineering via SICAM WEB.