Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 393
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
1000000000000000.000
select_execute_t Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary. 0 = no select command is
expected (direct command transmission)
0 to 6553.5
Fail_behav Behavior at failure
Keep
Substitute value
block Blocking (=not used) (S)
NO/YES
X_0% Nominal range in the physical unit of the
input/output (0%) (S)
-10.0 to 10.0
X_100% Nominal range in the physical unit of the
input/output (100%)
-10.0 to 10.0
Y_0% Technological or normalized value 0% (S)
-1000000000000000.000 to
1000000000000000.000
Y_100% Technological or normalized value 100% (S)
-1000000000000000.000 to
1000000000000000.000
receive format Source of datapoint
spontaneous
termination_t Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element