148/245 
Building Technologies Division  Basic Documentation LME7...   CC1P7105en 
Infrastructure & Cities Sector  19 PME73.840...  29.11.2011 
 
19 PME73.840...  
19.1 Program sequence PME73.840...  
 To connection diagram fuel trains (G)/(Gp1/1)/(Gp1/2) 
7105d77e/0611
M
Z
V1
V2
AL
K1X2-02 Pin 3
Actuator position
High-fire
Low-fire
Ignition laod
CLOSE
R
LR-OPEN
LR-CLOSE
LP
Pmin
P LT
ION / QRA
X3-04 Pin 5
Relay
contact
Function / inputs
Display and operating unit parameter number
LED permanent
LED flashing
tw      t11 t10          t12    t3    t3n          t4              t11 td4   td1  td3   td2
Standby         Startup       Operation       Shutdown        Valve proving
If parameter
                                   P241.00 =1 (ON)
Can be 
parameterized
t1        
TSA
224    225   226 257     230 231  232  234
Relay
contact
Function / outputs
SK
X3-04 Pin 1
X5-03 Pin 1
X5-03 Pin 3
X65 Pin 1
X5-03 Pin 2
X65 Pin 1
X3-02 Pin 1
X5-01 Pin 2
X2-02 Pin 4
X9-04 Pin 2
PV
SV
K1X6-03 Pin 3
K4X2-01 Pin 3
K5X4-02 Pin 3
K2/2X7-01 Pin 3
K7X7-04 Pin 4
X7-02 Pin 3
K2/1X2-03 Pin 3
Phase number 7 segment in the LME...
21 22 24 22 30  30  38 40 42  44 50 50 72 74 10  80 81 82 83 
t9             t5             
SA-NL
K11X2-09 Pin 3
SA-KL
K12X2-09 Pin 2
SA-ZU
X2-09 Pin 1
SA-R
X2-09 Pin 4
Input Dbr3 for PV
X2-09 Pin 8
Output PVX2-09 Pin 7
36 
260 
t22
74 
t8      
242 243 244 245259
POC
POC
*) *) *) *) *)
K4
K2/2
Phase number AZL2...
21 22 24 22 30  30  38 40 42  44 50 50 72 74 10  80 81 82 83 36 74 
240240240240240240
t11 t12
 
Figure 75: Program sequence PME73.840... to connection diagram fuel trains (G)/(Gp1/1)/(Gp1/2) 
*)  During the actuator running phases, the actuator feedback signal must be OFF first, then ON. 
*1  Valve proving, if P241.00 = 1 after mains ON, lockout or P234 (postpurge time t8) or  
  P241.01 = 0 second 
*2  Valve proving, if P241.00 = 1 and P234 (postpurge time t8) >0 second and P241.01 = 1