6.4  Control sequence in the event of fault 
 
If lockout occurs, the outputs for the fuel valves, the burner motor and the ignition 
equipment are immediately deactivated (<1 second). 
 
Cause  Response 
Mains voltage failure 
Restart 
Voltage below undervoltage threshold 
Safety shutdown 
Voltage above undervoltage threshold 
Restart 
Extraneous light before safety time   Lockout 
Extraneous light during waiting time   Start prevention, lockout after approx.  
30 seconds at the latest 
No flame at the end of safety time   Lockout end of safety time  
Loss of flame during operation  Factory setting: 
Lockout 
 
Can be parameterized: 
(Depending on program module, e.g. 
PME73.8...) 
1 x repetition 
Air pressure switch has welded in the 
operating position 
Start prevention, lockout after 30 seconds 
Air pressure switch has welded in the no-
load position 
Lockout at the end of the specified time  
No air pressure signal on completion of the 
specified time  
Lockout, with breakdown time ≥0.3 seconds 
POC contact is open during startup  Lockout, approx. 5 seconds after 
temperature thermostat or pressurestat or 
temperature or pressure switch on 
Pressure switch-min: Failure during 
operation 
Shutdown and start prevention 
 
In the event of lockout, the LME7… remains locked and the red fault signal lamp lights 
up. The burner control can immediately be reset. This state is also maintained in the 
event of mains failure. 
 
6.5  Resetting the burner control 
 
When lockout occurs, the burner control can immediately be reset. To do this, press the 
lockout reset button (info button) for about 1 second (<3 seconds). The LME7… can 
only be reset when all contacts in the line are closed and when there is no 
undervoltage.