Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 25 Operation via internal LED 29.11.2011
25.6 First startup with a new program module or
in case of replacement of program module
Alternately
Display shows alternately rSt and PrC.
Display shows the replacement of the program module.
Signal lamp blinks red once and yellow twice alternately.
Press
nfo
for >3 seconds to start data download from the
program module.
Signal lamp blinks yellow.
The process of 3 seconds is supported by a short flash of
the yellow signal lamp.
nfo
>3 s
Note:
If you press
nfo
for <3 seconds, data download does not
start. To start the restore process again, the LME7... must
be reset by switching mains ON/OFF.
Display shows run during download (restore process) of the
program sequence.
Alternately
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the unit changes to Loc 138
LCD Bild 06/0908
Alternately
After the restore process, the unit is automatically in
the lockout position (LOC 138) and must be reset for
operation!

Table of Contents

Other manuals for Siemens LME7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LME7 Series and is the answer not in the manual?

Siemens LME7 Series Specifications

General IconGeneral
BrandSiemens
ModelLME7 Series
CategoryController
LanguageEnglish

Related product manuals