164/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  21 Multistage or modulating mode  29.11.2011 
 
21.1.2  Connection diagram for load controller 
 
 
Note: 
The connection diagram shown is merely an example which must be verified in the 
individual case depending on the application! 
 
PME7... 
X65
0-135
7105d40/1210
0-135
X65
0-10V
0-20mA
4-20mA
LR
 
Figure 85: Connection diagram for load controller 
 
21.2 Actuators 
 
The LME7... has terminals for the connection of electromotoric actuators for the control 
of air dampers and regulating dampers of oil and gas burners. 
 
Possible types of actuator: 
 
Type 
Data 
Sheet 
Operating mode ¹) 
stage/modulating 
via 3-position step
input X5-03 
Operating mode ¹) 
modulating via 
analog input  
signal X65 
Potentiometer
ASZxx.3x 
SQN3...  N7808  x  x  x 
SQN7...  N7804  x  x  x 
SQM2...  N7812  x  x  x 
SQM40... 
SQM41... 
N7817  x  x  x 
SQM5...  N7815  x  x  x 
 
¹) Depending on the program sequence of LME7... or in the PME7... 
 
21.3 Function 
 
The internal program cycle time of the LME7... is about 0.147 s ( 0.15 s). 
In each 
program sequence, each input is read and the outputs are switched on or off 
accordingly.