217/245
Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 25 Operation via internal LED 29.11.2011
25.8 Manual restore
-
and
+
>1 s
Press
-
and
+
simultaneously for >1 second (Escape)
for starting the manual restore process.
Parameter PrC appears.
Display: PrC
-
or
+
Press
-
or
+
for parameter rSt.
Display: rSt
nfo
1…3 s
run appears during download (restore process) of program
sequence.
Alternately
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the unit changes to
Loc 138
LCD Bild 06/0908
Alternately
After the restore process, the unit is automatically in
the lockout position (LOC 138) and must be reset for
operation!
nfo
>1 s
LCD Bild 02/0908
Press
nfo
for >1 second to reset the unit.