Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 25 Operation via internal LED 29.11.2011
25.7 Manual backup
-
and
+
>1 s
Press
-
and
+
simultaneously for >1 second (Escape)
to start a manual backup process.
Parameter PrC appears.
Display: PrC
-
or
+
Press
-
or
+
for parameter bAC.
Display: bAC
nfo
1…3 s
run appears during download (backup process) of the
program sequence.
Alternately
Display shows alternately End and bAC.
Display shows the end of data exchange.
Display appears for 2 minutes or can be finished by pressing
nfo
.

nfo
>1 s
LCD Bild 02/0908
When the backup process is completed, the display shows
OFF.
Press
nfo
for >1 second to reset the unit.
Display: OFF
Warning!
If any parameters are changed, a backup must be made!