Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 23 Operation via AZL2… 29.11.2011
Press
for value 1.
Display: Value 1 blinks
/
reset
Press
/
reset
to activate the backup process.
Display shows run
<3 s
After approx. 3 seconds (depending on the duration of the
program sequence), the displays shows bAC End and
signals the end of the backup process.
Display: bAC End
It will now be displayed for 2 minutes, or can be finished by pressing the
/
reset
button
<2
min
or
/
reset
Display shows OFF when the backup process is finished.
Note:
During backup, all settings and parameters are transferred from the basic unit’s memory to the
memory of the program module.
Warning!
If any parameters are changed, a backup must be made! If this is not observed, there is a
risk of loss of safety functions.