Infrastructure & Cities Sector 24 Error code list with operation via external AZL2... display 29.11.2011
PWM (P675.00) after reaching the prepurge speed,
or
- After reaching the ignition load speed, the
maximum ignition load PWM (P675.01) was
exceeded
Loc: 226 PWM fan faulty
Parameterization error:
- Speed low-fire > speed high-fire, or
- Low-fire = 0 rpm, or
- Maximum speed = 0 rpm
Loc: 227 PWM fan faulty
One or several parameters violate the
minimum/maximum limit
rSt Er1
Error in compatibility program module to basic
unit during restore process
- Program sequence of program module does not
match the basic unit
rSt Er2
Error in compatibility program module to basic
unit during restore process
- Hardware of basic unit does not match the
program module
rSt Er3 Error during restore process
- Program module faulty
- Program module removed during restore
process