220/245
Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 26 Error code list with operation via internal LED 29.11.2011
Loc: 225 Faulty PWM fan
- Fan speed dropped below the minimum
prepurge PWM (P675.00) after reaching the
prepurge speed, or
- After reaching the ignition load speed, the
maximum ignition load PWM (P675.01) was
exceeded
Loc: 226 Faulty PWM fan
Parameterization error:
- Speed low-fire > speed high-fire, or
- Low-fire = 0 rpm, or
- Maximum speed = 0 rpm
Loc: 227 Faulty PWM fan
One or several parameters violate the
minimum/maximum limit
rSt Er1
Error in compatibility program module to
basic unit during restore process
- Program sequence of program module does not
match the basic unit
rSt Er2
Error in compatibility program module to
basic unit during restore process
- Hardware of basic unit does not match the
program module
rSt Er3 Error during the restore process
- Program module faulty
- Program module removed during restore
process