Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 4 Technical data 29.11.2011
Ionization probe
LME7...
M
C
ION
X10-05/2
X10-05/1
Figure 4: Measuring circuit for ionization probe
Legend
C Electrolytic condenser 100...470 µF; DC 10...25 V
ION Ionization probe
M
Microammeter Ri max. 5,000
Warning!
Simultaneous operation of QRA... and ionization probe is not permitted!
If not observed, there is a risk of impairment of safety functions.
Measuring circuit for detector
current measurement