Setting options
3RW5 HMI High Feature (󹪝rmware version V3.1 or higher)
Menu: "Parameter > Communication Module > OPC UA server" (if OPC UA server is activated)
You will 󹪝nd more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
User program via data set 132 (Page 163)
Parameter
Parameter Description
Port
Factory setting: 4 840
Adjustment range: 1 024 ... 49 151
In steps of: 1
8.4.5 Setting security functions
The OPC UA server and OPC UA client authorize each other for data exchange by exchanging
certi󹪝cates. By default, the 3RW5 OPC UA server classi󹪝es every certi󹪝cate of an OPC UA client
as "trustworthy". You can additionally encrypt the data tra󹪟c.
Requirements
The current clock time and date are stored in the 3RW55 or 3RW55 Failsafe soft starter (manually
or with NTP (Page 90)).
Note
Con󹪝guration of the OPC UA server
When con󹪝guring the OPC UA server, make sure that you only release security parameters that
are compatible with the protection concept of your machine or plant.
Functions
8.4 OPC UA server
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 113