Note
In "Automatic" mode, the PLC speci󹪝es the process image of the outputs. In this case, reading of
data set 68 returns the process image of the outputs as transmitted by the PLC.
Additional information
The following table describes the assignment of the process images "Parameter set bit 0" and
"Parameter set bit 1":
Parameter set Parameter set bit 0 Parameter set bit 1
Process image error 1 1
Parameter set 1 (PS1) 0 0
Parameter set 2 (PS2) 1 0
Parameter set 3 (PS3) 0 1
A.4.5.2 Data set 69: Process image input (PII)
Only read (r) access to the process image inputs (PII) is possible.
Byte Data format Meaning 3RW
50
1)
52
2)
55 /
55-F
3)
0 Unsigned8 Coordination x x x
2 Unsigned8 Slot number x x x
4 Unsigned16 Length of data structure x x x
6 Unsigned16 Start position x x x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
Byte Bit Data format Process image 3RW
50
1)
52
2)
55 /
55-F
3)
12 0 Bool Ready (automatic) r r r
1 Bool Motor On r r r
2 Bool Group error r r r
3 Bool Group warning r r r
4 Bool Input 1 r r r
5 Bool Input 2 - - r
6 Bool Input 3 - - r
7 Bool Input 4 - - r