Byte Bit Data format Parameter Range of values
[encoding]
In
steps of
3RW5
PN HF
1), 2)
[D
3)
]
16 0 Unsigned32 Port 1 024 ... 49 151
[1 024 ... 49 151]
1 r/w
[4 840]
20 0 Unsigned32 OPC UA Session Time-Out 10 ... 600 s
[10000 ... 600000]
1 ms r/w
[30000]
48 0 Bool No Security [0 ... 1] - r/w
[0]
[0] Disable
[1] Enable
1 Bool Basic128RSA15 - sign [0 ... 1] - r/w
[0]
[0] Disable
[1] Enable
2 Bool Basic128RSA15 - sign and encrypt [0 ... 1] - r/w
[0]
[0] Disable
[1] Enable
3 Bool Basic256 - sign [0 ... 1] - r/w
[0]
[0] Disable
[1] Enable
4 Bool Basic256 - sign and encrypt [0 ... 1] - r/w
[0]
[0] Disable
[1] Enable
5 Bool Basic256SHA256 - sign [0 ... 1] - r/w
[0]
[0] Disable
[1] Enable
6 Bool Basic256SHA256 - sign and encrypt [0 ... 1] - r/w
[1]
[0] Disable
[1] Enable
49 ...
119
- - Reserved - - -
1)
Supported by PROFINET High Feature communication module SIRIUS 3RW5 from rmware version V2.0
2)
Soft starter 3RW55 with rmware version V2.1.1 or higher or soft starter 3RW55 Failsafe with rmware version V1.1.0 or
higher
3)
Default encoding
A.4.5 3RW5 soft starter (slot 2)
A.4.5.1 Data set 68: Process image output (PIQ)
Read (r) and write (w) access to the process image output (PIQ) is possible.
Note
Note that data set 68 is overwritten by the cyclic process image in "Automatic" mode.
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules