Error codes (bytes) Error message Cause
high low
80
H
C2
H
Temporary lack of resources in the device
No free input bu󹪜er
The data set is currently being updated
The data set request is currently active on another
interface
80
H
C3
H
Resource not available
Module not available
7.5 Disable or enable group error and group warning
With the parameters "Group error" and "Group warning" you determine whether interrupts (error
interrupts and maintenance interrupts) are transmitted via PROFINET. In the factory setting,
Group error and Group warning are enabled and alarms (error alarms and maintenance alarms)
are transmitted
Setting options
You can disable or enable transmission of error interrupts (group error) and maintenance
interrupts (group warning) via the bus connection in the following ways:
Con󹪝guration software of the controller, e.g. STEP 7
User program via data set 131 (Page 162)
SIRIUS Soft Starter ES (TIA Portal) Premium / Professional via 3RW5 communication module
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" >Window "Work area" > "Communication module > Group error / Group
warning"
SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
via 3RW5 communication module
3RW5 HMI High Feature (Page 80)