Note
I&M data
I&M0 data is assigned for all of the devices (3RW5 communication module, 3RW5 soft starter
and 3RW5 HMI High Feature) and can be read out. Only the proxy for the "Station" (Slot 0) has
adjustable and readable I&M1, I&M2 and I&M3 data. The "Station" comprises the following
devices:
• 3RW5 communication module (slot 1)
• 3RW5 soft starter (slot 2)
• 3RW5 HMI High Feature (slot 3)
Note
Access to I&M data
With PROFINET, the I&M data can also be accessed via data sets 0xAFF0 to 0xAFF3 (PNO).
A.4.7.1 Data set 231: I&M0 - Device identication
Only read access (r) is possible to the device identication (I&M0).
Byte Data length Content
0 10 byte I&M header
Byte Data length Content Meaning Access
10 2 bytes MANUFACTURER_ID 42 = Manufacturer ID SIEMENS r
12 20 bytes ORDER_ID Article number r
32 16 bytes SERIAL_NUMBER Serial number r
48 2 bytes HARDWARE_REVISION Product version r
50 4 bytes SOFTWARE_REVISION Firmware version r
54 2 bytes REV_COUNTER Provides information about the parameterized
changes on the device.
r
56 2 bytes PROFILE_ID Gives information about the prole supported by
the device and the line of products belonging to
the device.
r
58 2 bytes PROFILE_SPECIFIC_TYPE Used to supplement the object "PROFILE_ID" and
contains further information on the prole.
r
60 2 bytes IM_VERSION Provides information about the version of the
identication data (0x0101 = Version 1.1).
r
62 2 bytes IM_SUPPORTED Provides information about the available identi‐
cation data (Index 2 to 4).
r
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
202 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004