Byte Data format Meaning 3RW55 /
55‑F
1)
4 Unsigned16 Length of data structure x
6 Unsigned16 Start position x
1)
Supported by SIRIUS soft starters 3RW55 and 3RW55 Failsafe
Object
No.
Byte Bit Data format Parameters Value range
[encoding]
Incre‐
ment
3RW55 /
55‑F
1)
[D
2)
]
2344 60 0 Bit4 Pump cleaning - mode [0 ... 1] - r/w
[0]
[0] Deactivated
[1] Manual
2345 60 4 Bit4 Pump cleaning - start/
stop parameters
[1 ... 5] - r/w
[5]
[1] Parameter set 1
[2] Parameter set 2
[3] Parameter set 3
[5] Operating parameters
2346 61 0 Unsigned8 Pump cleaning - time 1 ... 30 s
[1 ... 30]
1 s r/w
[20]
2347 62 0 Unsigned8 Pump cleaning - cycles 1 ... 10
[1 ... 10]
1 r/w
[3]
2353 80 0 Bit4 Sensorless motor stand‐
still detection
[0 ... 1] - r/w
3), 4)
[1]
[0] Disable
[1] Enable
- 81 ...
199
- - Reserved - - -
1)
Supported by SIRIUS soft starters 3RW55 and 3RW55 Failsafe
2)
Default encoding
3)
3RW55 soft starter from 󹪝rmware version V2.0
4)
Not supported by SIRIUS 3RW55 Failsafe soft starter
A.4.5.11 Data set 135: Parameter cyclic process image
Read (r) and write (w) access is possible to the parameter cyclic process image. Data set 135 is
not supported by the 3RW50 and 3RW52 soft starters.
Byte Data format Meaning 3RW55 /
55‑F
1)
0 Unsigned8 Coordination
[0x21] Write via acyclic bus channel – user program
x
2 Unsigned8 Slot number x
4 Unsigned16 Length of data structure x
6 Unsigned16 Start position x
1)
Supported by SIRIUS soft starters 3RW55 and 3RW55 Failsafe
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
194 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004