7.7 Messages about the mode
The following message bits in data set 92 of the 3RW5 soft starter (slot 2) (Page 168) clearly
indicate which control source currently has control priority:
Automatic mode ()
Automatic operation - input controlled ()
1)
Operating mode manual - bus ()
Manual operation bus - PC controlled ()
Manual operation bus - Webserver controlled ()
Operating mode manual - local ()
Manual operation local - input controlled ()
Manual operation local - HMI controlled ()
Manual operation local - PC controlled ()
Connection abort in manual mode ()
Automatic Manual Control priority is with:
Manual operation
bus
Manual operation local
1)
0 0 0 0 0 0 0 0 0 0 Message is not permitted.
1 0 0 0 0 0 0 0 0 0 PLC controls via 󹪝eldbus.
0 1 0 0 0 1 1 0 0 0 Control digital inputs.
2)
0 0 1 0 0 0 0 0 0 1 No control source.
0 0 1 1 0 0 0 0 0 0 PC controls via 󹪝eldbus.
0 0 1 0 1 0 0 0 0 0 Web server controls via 󹪝eldbus.
0 0 0 0 0 1 0 0 0 1 No control source.
0 0 0 0 0 1 1 0 0 0 Input IN or control digital inputs.
3)
0 0 0 0 0 1 0 1 0 0 HMI controls.
0 0 0 0 0 1 0 0 1 0 PC controls via local interface.
1)
Supported by soft starter 3RW55 with 󹪝rmware version V2.1 or higher and soft starter 3RW55 Failsafe with 󹪝rmware version
V1.1.0 or higher
2)
Combination of the message bits not possible for 3RW50, 3RW52, 3RW55 soft starters with 󹪝rmware version earlier than V2.1
and 3RW55 Failsafe soft starters with 󹪝rmware version V1.0.0. For soft starters 3RW55 from 󹪝rmware version V2.1 and soft
starters 3RW55 Failsafe with 󹪝rmware version V1.1.0 or higher if the digital inputs have master control by activating the
"Manual operation local - input controlled" bit in the process image output (PIQ). The PLC can fetch back control at any time.
3)
Combining the message bits is possible for 3RW50, 3RW52, 3RW55 and 3RW55 Failsafe soft starters. For soft starters 3RW55
from 󹪝rmware version V2.1 and soft starters 3RW55 Failsafe with 󹪝rmware version V1.1.0 or higher only if the input action
"Operating mode manual - local" has been parameterized and activated.
For more information on setting the operating mode, see chapter Operating modes and master
control function (Page 24).
Messages and diagnostics
7.7 Messages about the mode
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 81