Byte Bit Data format Parameter Range of values
[encoding]
3RW5 PN
Std
1)
[D
3)
]
HF
2)
[D
3)
]
11 1 Bool Operation without PN control [0 ... 1] - r/w
4), 5)
[0]
[0] No
[1] Yes
4 Bool Web server [0 ... 1] - r/w
4), 5)
[0]
[0] Disable
[1] Enable
5 Bool OPC UA server [0 ... 1] - r/w
4), 5)
[0]
[0] Disable
[1] Enable
12 ...
15
- - Reserved - - -
1)
Supported by SIRIUS 3RW5 PROFINET Standard communication module
2)
Supported by SIRIUS 3RW5 PROFINET High Feature communication module
3)
Default encoding
4)
3RW5 PROFINET High Feature communication module from 󹪝rmware version V2.0
5)
Soft starter 3RW55 with 󹪝rmware version V2.1.1 or higher or soft starter 3RW55 Failsafe with 󹪝rmware version V1.1.0 or
higher
A.4.4.3 Data set 132: Parameter communication server (slot 1)
Read (r) and write (w) access to the parameter communication servers is possible. Data set 132
of the 3RW5 communication module (slot 1) is only supported by the 3RW5 PROFINET High
Feature communication module from 󹪝rmware version V2.0.
Byte Data format Meaning 3RW
50
1)
52
2)
55 /
55‑F
3)
0 Unsigned8 Coordination
[0x21] Write via acyclic bus channel – user program
x x x
2 Unsigned8 Slot number x x x
4 Unsigned16 Length of data structure x x x
6 Unsigned16 Start position x x x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 163