Siemens PROFINET SIRIUS 3RW5 - Data Set 133: Parameter Extended Functions 2

Siemens PROFINET SIRIUS 3RW5
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Object
No.
Byte Bit Data format Parameters Value range
[encoding]
Incre‐
ment
3RW55 /
55‑F
1)
[D
3)
]
2341 179 0 Unsigned8 Current lower limit -
maintenance demanded
19 … 100 %
[19 … 100]
1 % r/w
[0]
[0] Deactivated
14 186 0 Bit4 Response to Ie upper
fault limit violation
2)
[0 ... 1] - r/w
[0]
[0] Do not turn o󹪜
[1] Turn o󹪜
2296 4 Bit4 Response to Ie lower lim‐
it fault violation
2)
[0 ... 1] - r/w
[0]
[0] Do not turn o󹪜
[1] Turn o󹪜
- 187 ...
199
- - Reserved - - -
1)
Supported by SIRIUS soft starters 3RW55 and 3RW55 Failsafe
2)
Parameter is only in data set 132
3)
Default encoding
4)
Parameter is relevant for EX applications
5)
3RW55 soft starter from 󹪝rmware version V2.1
6)
Not supported by SIRIUS 3RW55 Failsafe soft starter
A.4.5.9 Data set 133: Parameter extended functions 2
Read (r) and write (w) access to the parameter extended functions 2 is possible.
Byte Data format Meaning 3RW
50
1)
52
2)
55 /
55‑F
3)
0 Unsigned8 Coordination
[0x21] Write via acyclic bus channel – user program
x x x
2 Unsigned8 Slot number x x x
4 Unsigned16 Length of data structure x x x
6 Unsigned16 Start position x x x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
Object
No.
Byte Bit Data format Parameters Value range
[encoding]
Incre‐
ment
3RW
50 /
52
1)
[D
3)
]
55 /
55‑F
2)
[D
3)
]
2222 40 0 Unsigned8 Analog output - signal
type
[0 ... 3] - r/w
[2]
r/w
[0]
[0] Deactivated
[2] 4-20mA
[3] 0-10V
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
192 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004