Byte Data format Measured value Value range Incre‐
ment
3RW
50 /
52
1)
55 /
55-F
2)
74 Unsigned16 Remaining switching frequency monitoring time 0 … 65 535 s 1 s - r
76 Unsigned8 Phase current average (%) 0 … 796.9 % 3.125 % r r
80 Signed32 Phase current average (rms) -20 000 … 20 000 A 0.01 A r r
84 Signed32 Maximum phase current (rms) -20 000 … 20 000 A 0.01 A - r
88 ...
99
- Reserved - - - -
1)
Supported by SIRIUS 3RW50 and 3RW52 soft starters
2)
Supported by SIRIUS 3RW55 and 3RW55 Failsafe soft starters
A.4.5.5 Data set 95: Statistic data
Only read (r) access to the statistic data is possible.
Byte Data format Meaning 3RW
50
1)
52
2)
55 /
55-F
3)
0 Unsigned8 Coordination x x x
2 Unsigned8 Slot number x x x
4 Unsigned16 Length of data structure x x x
6 Unsigned16 Start position x x x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
Byte Data format Statistic data Value range Incre‐
ment
3RW
50 /
52
1)
55 /
55-F
2)
12 Unsigned8 Phase current max (%) 0 … 796.9 % 3.125 % r r
14 Unsigned16 Last tripping current IA (%) 0 … 1 000 % 3.125 % r r
16 Unsigned32 Operating hours - device 0 … 4 294 967 295 s 1 s r r
20 Unsigned32 Number of starts motor CW 0 … 4 294 967 295 1 r r
24 Unsigned32 Number of starts motor CCW 0 … 4 294 967 295 1 - r
28 Unsigned16 Number of motor overload trips 0 … 65 535 1 r r
32 Signed32 Maximum phase current (rms) -20 000 … 20 000 A 0.01 A r r
36 Signed32 Last tripping current IA (rms) -20 000 … 20 000 A 0.01 A r r
40 Unsigned32 Operating hours - motor 0 … 4 294 967 295 s 1 s r r
44 Unsigned32 Operating hours - motor current = 18 ... 49.9% x
Iemax
0 … 4 294 967 295 s 1 s r r
48 Unsigned32 Operating hours - motor current = 50 ... 89.9% x
Iemax
0 … 4 294 967 295 s 1 s r r
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
174 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004