A.4.7.2 Data set 232: I&M1 - Equipment identi󹪝er
Read (r) and write (w) access to the (I&M1) equipment identi󹪝er is possible.
Note
Validity of the write access
The 3RW5 soft starter checks the validity of the write access. The ASCII characters 0x20 ‑ 0x7E
are accepted. If the 3RW5 soft starter does not accept the data of the write access, the
3RW5 communication module responds with a negative acknowledgment.
Byte Data format Meaning
0 ... 9 - I&M header
0 Unsigned8 Coordination
[0x21] Write via acyclic bus channel – user program
1 ... 9 - Transfer the value 0x00 for writing the data set for bytes 1 ... 9.
Byte Data length Content Meaning Access
10 32 bytes TAG_FUNCTION Plant identi󹪝er
Fill unused positions with blanks (0x20).
r/w
42 22 bytes TAG_LOCATION Location designation
Fill unused positions with blanks (0x20).
r/w
A.4.7.3 Data set 233: I&M2 - Installation
Read (r) and write (w) access to the (I&M2) installation is possible.
Note
Validity of the write access
The 3RW5 soft starter checks the validity of the write access. The accepted display formats are
"YYYY‑MM‑DD" (year-month-day) and "YYYY‑MM‑DD HH:MM" (year-month-day hour:minute). If
the 3RW5 soft starter does not accept the data of the write access, the 3RW5 communication
module responds with a negative acknowledgment.
YYYY (year): 0001 - 9999
MM (month): 01 - 12
DD (day): 01 - 31 (depending on month)
HH (hour): 00 - 23
MM (minute): 00 - 59
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 203