Parameter
Parameter Description SecurityPolicy MessageSecurity‐
Mode
No Security
Disable (factory setting)
Enable
None NONE
Basic128RSA15 - sign
Disable (factory setting)
Enable
Basic128RSA15 SIGN
Basic128RSA15 - sign and encrypt
Disable (factory setting)
Enable
Basic128RSA15 SIGNANDENCRYPT
Basic256 - sign
Disable (factory setting)
Enable
Basic256 SIGN
Basic256 - sign and encrypt
Disable (factory setting)
Enable
Basic256 SIGNANDENCRYPT
Basic256SHA256 - sign
Disable (factory setting)
Enable
Basic256SHA256 SIGN
Basic256SHA256 - sign and encrypt
Disable
Enable (factory setting)
Basic256SHA256 SIGNANDENCRYPT
8.4.6 OPC UA Session Time-Out
The parameter "OPC UA Session Time-Out" determines how long an OPC UA client connection
remains open without activity. If the OPC UA client does not make a service request within this
time interval, the OPC UA server terminates the OPC UA client connection.
Setting options
3RW5 HMI High Feature (󹪝rmware version V3.1 or higher)
Menu: "Parameter > Communication Module > OPC UA server" (if the OPC UA server is
activated)
You will 󹪝nd more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
User program via data set 132 (Page 163)
Parameter
Parameter Description
OPC UA Session Time-Out
Factory setting: 30 s
Adjustment range: 10 ... 600 s
In steps of: 1 ms
Functions
8.4 OPC UA server
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 115