7.4 Error codes for negative data set acknowledgement
If a data set is rejected, an error code is sent with the negative acknowledgment. The error code
provides information about the reason for the negative acknowledgment.
Evaluation of the error codes
You can evaluate the error codes in the following ways:
Con󹪝guration software of the controller, e.g. STEP 7
The error codes are output via PROFINET IO Layer 2. Further information can be found in the
corresponding manuals in the PROFINET IO protocol description.
Error codes
Error codes (bytes) Error message Cause
high low
00
H
00
H
No error -
Communication interface
80
H
A0
H
Negative acknowledgment for "Read data
set"
Data set write-only
80
H
A1
H
Negative acknowledgment for "Write data
set"
Data set read-only
80
H
A2
H
Protocol error
Layer 2 (󹪝eldbus)
Device interface
Incorrect coordination
80
H
A9
H
This function is not supported.
Acyclic communication is not equal to Read/Write
data set.
Access to technology
80
H
B0
H
Unknown data set number
Data set number is not supported by the soft starter.
80
H
B1
H
Incorrect data set length when writing
Data set length and speci󹪝ed data set length di󹪜er‐
ent
80
H
B2
H
Wrong slot number
Incorrect slot number
80
H
B3
H
Inconsistent con󹪝guration
Invalid parameter value pairings
80
H
B4
H
Incorrect data set length when reading
Data set length and speci󹪝ed data set length di󹪜er‐
ent
80
H
B6
H
Communication partner has rejected data
transfer.
Incorrect operating mode
Data set is read-only
Parameters cannot be changed in ON state
80
H
B7
H
Invalid value range
Incorrect value range
80
H
B8
H
Given parameter is invalid
Incorrect parameter value
Device resources
Messages and diagnostics