5.1.3 Removing the COM connecting cable on the 3RW5 communication module
Requirements
3RW5 communication module mounted on a level surface (Page 41)
Removed bus connector (󹪝eldbus) (Page 51)
Cover cap
NOTICE
Damage to property due to electrical voltage
Switch o󹪜 the power to the 3RW5 soft starter before starting work (main and control supply
voltage).
Procedure
Illustration similar
1. Loosen die securing mechanism on the bus connector of the COM connecting cable.
2. Pull the bus connector of the COM connecting cable out of the plug-in connection of
the 3RW5 communication module.
Result
You have disconnected the 3RW5 communication module from the 3RW50 soft starter. Place the
cover cap onto the front plug-in connection of the 3RW5 communication module.
Connection
5.1 COM connecting cable
SIRIUS 3RW5 PROFINET communication modules
48 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004