Object
No.
Byte Bit Data format Parameters Value range
[encoding]
Incre‐
ment
3RW55 /
55‑F
1)
[D
3)
]
2240 72 0 Unsigned8 Response to ON-com‐
mand during active mon‐
itoring time
2)
[0 ... 3] - r/w
[3]
[0] Turn o without restart
[1] Turn o with restart
[2] Warning without lock-out
[3] Warning with lock-out
2242 75 0 Bit4 Emergency start
2)
[0 ... 1] - r/w
4)
[1]
[0] Disable
[1] manually enable/disable
2243 76 0 Bit4 Emergency run
2)
[0 ... 2] - r/w
4), 5), 6)
[0]
[0] Disable
[1] Manually enable/disable
[2] Enable
2251 82 0 Unsigned16 Active power upper limit
error
0 … 400 %
[0 … 400]
1 % r/w
[0]
2252 84 0 Unsigned16 Active power upper limit
- maintenance deman‐
ded
0 … 400 %
[0 … 400]
1 % r/w
[0]
2254 88 0 Unsigned8 Active power lower limit
error
0 … 100 %
[0 … 100]
1 % r/w
[0]
2255 89 0 Unsigned8 Active power lower limit
- maintenance deman‐
ded
0 … 100 %
[0 … 100]
1 % r/w
[0]
2260 96 0 Bit4 Response to P upper
fault limit violation
2)
[0 ... 1] - r/w
[0]
[0] Do not turn o
[1] Turn o
2297 4 Bit4 Response to fault P low‐
er limit violation
2)
[0 ... 1] - r/w
[0]
[0] Do not turn o
[1] Turn o
2250 104 0 Unsigned32 Active power reference
value
0 … 2 000 000 W
[0 … 2 000 000]
1 W r/w
[0]
2317 154 0 Unsigned16 Starting time upper limit
- maintenance deman‐
ded
0 … 400 %
[0 … 400]
1 % r/w
[0]
2320 159 0 Unsigned8 Starting time lower limit
- maintenance deman‐
ded
0 … 100 %
[0 … 100]
1 % r/w
[0]
2337 172 0 Unsigned16 Current upper limit error 50 … 400 %
[50 … 400]
1 % r/w
[0]
[0] Deactivated
2338 174 0 Unsigned16 Current upper limit -
maintenance demanded
50 … 400 %
[50 … 400]
1 % r/w
[0]
[0] Deactivated
2340 178 0 Unsigned8 Current lower limit error 19 … 100 %
[19 … 100]
1 % r/w
[0]
[0] Deactivated
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 191