Tag NodeId.
Identier
Data format Unit
Displayed name and level Browse name i =
1s
t
2n
d
3r
d
4th level
Active power Active_power_MESW 1082 Float kW
Asymmetry Asymmetry_MESW 1083 UInt32 %
Line frequency Line_frequency_MESW 1084 Float Hz
Line voltage U L1-L2 (rms) Line_volt‐
age_U_L1_L2_rms_MESW
1085 Float V
Line voltage U L2-L3 (rms) Line_volt‐
age_U_L2_L3_rms_MESW
1086 Float V
Line voltage U L3-L1 (rms) Line_volt‐
age_U_L3_L1_rms_MESW
1087 Float V
Motor temperature rise Motor_temperature_rise_MESW 1088 UInt32 %
Output frequency Output_frequency_MESW 1089 Float Hz
Phase current average (%) Phase_current_average_per‐
cent_MESW
1090 Float %
Phase current average (rms) Phase_current_aver‐
age_rms_MESW
1091 Float A
Phase current I L1 (%) Phase_current_I_L1_per‐
cent_MESW
1092 Float %
Phase current I L1 (rms) Phase_current_I_L1_rms_MESW 1093 Float A
Phase current I L2 (%) Phase_current_I_L2_per‐
cent_MESW
1094 Float %
Phase current I L2 (rms) Phase_current_I_L2_rms_MESW 1095 Float A
Phase current I L3 (%) Phase_current_I_L3_per‐
cent_MESW
1096 Float %
Phase current I L3 (rms) Phase_current_I_L3_rms_MESW 1097 Float A
Phase current max (rms) Phase_current_max_rms_MESW 1098 Float A
Power factor L1...3 Power_factor_L1...3_MESW 1099 Float -
Remaining motor cooling time Remaining_motor_cool‐
ing_time_MESW
1100 Float s
Remaining switching element cooling
time
Remaining_switching_ele‐
ment_cooling_time_MESW
1101 Float s
Remaining switching frequency monit.
time
Remaining_switching_frequen‐
cy_monit._time_MESW
1102 UInt32 s
Remaining time for motor overload pro‐
tection
Remaining_time_for_motor_over‐
load_protection_MESW
1103 Float s
Switching element heating Switching_element_heat‐
ing_MESW
1104 UInt32 %
Model Model 1016 Localized‐
Text
-
ParameterSet ParameterSet 1023 - -
Functions
8.4 OPC UA server
SIRIUS 3RW5 PROFINET communication modules
124 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004