Byte Data format Maximum pointer Value range Incre‐
ment
3RW
50 /
52
1)
55 /
55-F
2)
16 Unsigned8 Maximum phase current I L1 (%) 0 … 796.9 % 3.125 % r r
17 Unsigned8 Phase current I L2 max (%) 0 … 796.9 % 3.125 % r r
18 Unsigned8 Phase current I L3 max (%) 0 … 796.9 % 3.125 % r r
20 Unsigned16 Maximum trigger current 0 … 1 000 % 3.125 % r r
22 Unsigned16 Number of motor overload trips 0 … 65 535 1 r r
24 Signed32 Maximum trigger current -20 000 … 20 000 A 0.01 A r r
28 Signed32 Minimum phase current I L1 (rms) -20 000 … 20 000 A 0.01 A r r
32 Signed32 Phase current I L2 min (rms) -20 000 … 20 000 A 0.01 A r r
36 Signed32 Phase current I L3 min (rms) -20 000 … 20 000 A 0.01 A r r
40 Signed32 Maximum phase current I L1 (rms) -20 000 … 20 000 A 0.01 A r r
44 Signed32 Phase current I L2 max (rms) -20 000 … 20 000 A 0.01 A r r
48 Signed32 Phase current I L3 max (rms) -20 000 … 20 000 A 0.01 A r r
52 Unsigned16 Line-to-line voltage U L1-L2 min 0 … 1 500 V 0.1 V - r
54 Unsigned16 Line-to-line voltage U L2-L3 min 0 … 1 500 V 0.1 V - r
56 Unsigned16 Line-to-line voltage U L3-L1 min 0 … 1 500 V 0.1 V - r
58 Unsigned16 Line-to-line voltage U L1-L2 max 0 … 1 500 V 0.1 V - r
60 Unsigned16 Line-to-line voltage U L2-L3 max 0 … 1 500 V 0.1 V - r
62 Unsigned16 Line-to-line voltage U L3-L1 max 0 … 1 500 V 0.1 V - r
69 Unsigned8 Maximum switching element heating 0 … 250 % 1 % r r
70 Unsigned8 Minimum line frequency 0 … 100 Hz 0.5 Hz - r
71 Unsigned8 Maximum line frequency 0 … 100 Hz 0.5 Hz - r
72 Unsigned32 Operating hours - motor current = 18 ... 49.9% x Ie 0 … 4 294 967 295 s 1 s r r
76 Unsigned32 Operating hours - motor current = 50 ... 89.9% x Ie 0 … 4 294 967 295 s 1 s r r
80 Unsigned32 Operating hours - motor current = 90 ... 119.9% x
Ie
0 … 4 294 967 295 s 1 s r r
84 Unsigned32 Operating hours - motor current = 120 ... 1000% x
Ie
0 … 4 294 967 295 s 1 s r r
88 Unsigned32 Operating hours - device 0 … 4 294 967 295 s 1 s r r
96 Signed32 Starting current I max (rms) -20 000 … 20 000 A 0.01 A r r
100 Signed32 Starting current I L1 max (rms) -20 000 … 20 000 A 0.01 A r r
104 Signed32 Starting current I L2 max (rms) -20 000 … 20 000 A 0.01 A r r
108 Signed32 Starting current I L3 max (rms) -20 000 … 20 000 A 0.01 A r r
112 Unsigned16 Number of starts with ext. bypass 0 … 65 535 1 r r
3), 4)
114 ...
125
- Reserved - - - -
1)
Supported by SIRIUS 3RW50 soft starter from rmware version V1.0 and 3RW52 from rmware version V2.0
2)
Supported by SIRIUS 3RW55 and 3RW55 Failsafe soft starters
3)
3RW55 soft starter from rmware version V2.0
4)
Not supported by SIRIUS 3RW55 Failsafe soft starter
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
176 Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004