EasyManua.ls Logo

Siemens PROFINET SIRIUS 3RW5 - Page 29

Siemens PROFINET SIRIUS 3RW5
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master
Control > Get Control"
Note
Fetching control from "Automatic operation - input controlled" mode
The "Automatic operation - input controlled" mode is possible for the following 3RW5 soft
starters:
3RW55 soft starter from 󹪝rmware version V2.1
Soft starter 3RW55 Failsafe with 󹪝rmware version V1.1.0 or higher
Giving back control
SIRIUS Soft Starter ES (TIA Portal) Premium / Professional actively passes master control to
"Automatic" mode in response to a command to this e󹪜ect.
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Control >
Release Control"
Withdrawal of control by other control sources
Control is withdrawn from the operating mode "Manual operation bus - PC controlled" by the
operating mode "Manual operation - local" as follows:
3RW50, 3RW52 soft starters and for 3RW55 and 3RW55 Failsafe soft starters if the input
action "Operating mode manual - local" is not parameterized: By activating the "Manual
operation local - input controlled" bit in the process image output (PIQ) (Page 154).
For 3RW55 and 3RW55 Failsafe soft starters if the input action "Operating mode manual -
local" is parameterized: By activating the input action "Operating mode manual - local".
"LOCAL / REMOTE" action on the 3RW5 HMI
Command in SIRIUS Soft Starter ES (TIA Portal) (local interface on the 3RW5 HMI High
Feature)
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master
Control > Get Control"
Operating mode "Manual operation bus - Webserver controlled"
Fetching control
The web server actively fetches master control from the "Automatic" mode or "Automatic
operation - input controlled" mode in response to a command to this e󹪜ect.
Web page "Control Panel" > "Master Control > Get Control"
Giving back control
The web server actively passes master control to "Automatic" mode in response to a command
to this e󹪜ect.
Web page "Control Panel" > "Master Control > Release Control"
Description
3.5 Operating modes and master control function
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004 29

Table of Contents

Related product manuals