1. Integrate the 3RW5 soft starter in the con󹪝guration software of the controller as the IO device
into the PROFINET IO system.
The following procedures are possible:
Integrating 3RW5 soft starter via HSP in STEP 7 (TIA Portal) (Page 62)
Integrating the 3RW5 Soft Starter into the PROFINET IO system with the GSDML 󹪝le
(Page 63)
Note
STEP 7 (TIA Portal) as of V16
3RW5 soft starters, 3RW5 communication modules and 3RW5 HMIs are already contained in
the HW catalog of STEP 7 (TIA Portal) as of V16. Check the 3RW5 topic page for updates and
ensure that your device and the current 󹪝rmware are contained in the HW catalog.
2. Enter a device name for the IO device in the con󹪝guration software of the controller (e.g. in
STEP 7 in the properties of the IO device).
Note the information in chapter Device name (Page 60).
3. Load the con󹪝guration into the IO controller.