EasyManua.ls Logo

Siemens SENTRON ATC6500 - Page 102

Siemens SENTRON ATC6500
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
7.2 General connection drawings
3KC ATC6500 transfer control device
100 Manual, 05/2019, L1V30538268002A-01
Terminal
Parameter code
Settings
-
P02.01 System configuration
2S – 1T SI or 2S 1T - AI
- P02.22 Management of the tie breaker (TB) Breaker pulse or breaker continuous
-
P08.01 Type of breaker
Breaker pulse or breaker continuous
40 (INP1)
P12.1.01 Function of the input INP1
Source 1 breaker closed (feedback 1)
41 (INP2)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
42 (INP3)
P12.3.01 Function of the input INP3
Tie breaker TB / NPL closed (feedback message)
43 (INP4)
P12.4.01 Function of the input INP4
Source 1 breaker protection (Trip 1)
44 (INP5)
P12.05.01 Function of the input INP5
Source 2 breaker protection (Trip 2)
45 (INP6)
P12.06.01 Function of the input INP6
Tie breaker protection (Trip)
55 (OUT1)
P13.1.01 Function of the output OUT1
Open Source 1 breaker
57 (OUT2)
P13.2.01 Function of the output OUT2
Close Source 1 breaker
58 (OUT3)
P13.3.01 Function of the output OUT3
Open Source 2 breaker
60 (OUT4)
P13.4.01 Function of the output OUT4
Close Source 2 breaker
20 (OUT7)
P13.7.01 Function of the output OUT7
Open tie breaker TB / NPL
31 (OUT9)
P13.9.01 Function of the output OUT9
Close tie breaker TB / NPL

Table of Contents