HF radiation according to IEC 61000-4-3
Electromagnetic HF 󹪝eld, amplitude-modulated
80 to 1000 MHz; 1.4 to 2 GHz 2.0 GHz to 2.7 GHz
10 V/m 3 V/m
80 % AM (1 kHz)
HF coupling
HF current feed according to IEC 61000-4-6
0.15 to 80 MHz
10 V
80 % AM (1 kHz)
Emission of radio interference
Interference emission of electromagnetic 󹪝elds according to EN 55016. Limit class A, group 1
(measured at distance of 10 m).
Frequency Interference emission
from 30 to 230 MHz < 40 dB (µV/m)Q
from 230 to 1000 MHz < 47 dB (µV/m)Q
Shipping and storage conditions
The ET 200iSP distributed I/O device exceeds the requirements in terms of transport and storage
conditions according to IEC 61131-2. The following speci󹪝cations apply for modules that are
transported or stored in their original packaging.
Type of condition permissible range
at user's discretion ≤ 1 m
Temperature from - 40 °C to + 70 °C
Temperature change 20 K/h
Barometric pressure from 1080 to 660 hPa (corresponds to an altitude of
-1000 to 3500 m)
Relative humidity from 5 to 95 %, without condensation
See also
General Rules and Regulations for Wiring (Page 119)
General technical speci󹪝cations
9.3 Electromagnetic compatibility, transport and storage conditions
ET 200iSP
244 Operating Instructions, 11/2022, A5E00247483-AK

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals