Technical specications
Article number 6ES7138-7EC00-0AA0
Supply voltage
Rated value (AC) 230 V; 120/230 V AC
Line frequency
• permissible range, lower limit
47 Hz
• permissible range, upper limit
63 Hz
Input current
from supply voltage L1, max. 1.04 A; at rated voltage 230 VAC:0.45A at rated
voltage 120 VAC:0.75A
Power loss
Power loss, typ. 5 W; 5 W + 1.2 x total power loss of the electronics
modules
Power loss, max. 21.3 W
Interrupts/diagnostics/status information
Status indicator Yes
Alarms No
Diagnoses
• Diagnostic information readable
Yes; via IM 152
Diagnostics indication LED
• Group error SF (red)
No
Potential separation
primary/secondary Yes
between supply voltage and electronics No
Standards, approvals, certicates
CE mark Yes
Use in hazardous areas
• ATEX marking
Ex de [ib]IIC T4
Dimensions
Width 60 mm
Height 190 mm
Depth 136.5 mm
Weights
Weight, approx. 2 700 g
Technical specications
Voltages, currents, electrical potentials
Nominal power supply voltage AC 120/230 V
2
• Power failure buering power bus
min. 20 ms
• Voltage failure backup interface module
min. 20 ms
• Power failure buering backplane bus
min. 20 ms
Insulation tested
Power Supply
11.2 Power supply PS 120/230 VAC
ET 200iSP
274 Operating Instructions, 11/2022, A5E00247483-AK