Measuring range for thermocouple type R, S
Table 14-25 SIMATIC S7 format: Measuring range type R, S in °C and °F
Types R, S
in °C
Units Types R, S
in °F
Units Range
Decimal Hexa‐
decimal
Decimal Hexa‐
decimal
> 2019.0 32767 7FFF
H
> 3276.6 32767 7FFF
H
Overow
2019.0
:
1769.1
20190
:
17691
4EDE
H
:
451B
H
3276.6
:
3216.3
32766
:
32163
7FFE
H
:
7DA3
H
Overrange
1769.0
:
-50.0
17690
:
-500
451A
H
:
FE0C
H
3216.2
:
-58.0
32162
:
-580
7DA2
H
:
FDBC
H
Nominal range
-50.1
:
-170.0
-510
:
-1700
FE0B
H
:
F95C
H
-58.1
:
-274.0
-581
:
-2740
FDBB
H
:
F54C
H
Underrange
< -170.0 -32768 8000
H
< -274.0 -32768 8000
H
Underow
Measuring range for thermocouple type T
Table 14-26 SIMATIC S7 format: Measuring range type T in °C and °F
Type T in °C Units Type T in °F Units Range
Decimal Hexa‐
decimal
Decimal Hexa‐
decimal
> 540.0 32767 7FFF
H
> 1004.0 32767 7FFF
H
Overow
540.0
:
400.1
5400
:
4001
1518
H
:
0FA1
H
1004.0
752.1
10040
7521
2738
H
1DC1
H
Overrange
400.0
:
-270.0
4000
:
-2700
0FA0
H
:
F574
H
752.0
:
-454.0
7520
:
-4540
1D60
H
:
EE44
H
Nominal range
< -270.0 -32768 8000
H
< -454.0 -32768 8000
H
Underow
Analog electronic modules
14.8 Representation of analog values
ET 200iSP
384 Operating Instructions, 11/2022, A5E00247483-AK