Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
128 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Trip level activity, warning level
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
Here you can specify in which motor operating states the trip level / warning level will be
active:
Always (on)
Trip level
/ warning level is always active, regardless
of whether the motor is running or at a standstill
If motor is on, except TPF (run)
Trip
level
/ warning level is only active when the motor
is running
If motor is on, except TPF, with
startup override (run+)
Trip level
/ warning level is only active when the motor
is running and starting has been completed
Response to trip level
Here you can set how SIMOCODE pro should respond if the trip level is overshot.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 28 Response to "trip level" in ground-fault monitoring
Response
Trip level
signaling
X (d)
warn
tripping
X
delay
0 to 25.5 s (default: 0.5 s)
1)
1) Extension of the residual current transformer delay

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals