Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
129
Response to warning level
Here you can set how SIMOCODE pro should respond if the warning level is overshot.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 29 Response to "warning level" in ground-fault monitoring
Response
Warning level
disabled
X (d)
signaling X
warn
X
tripping
delay
0 to 25.5 s (default: 0.1 s)
1)
1) Extension of the residual current transformer delay
Hysteresis
Here you can set the hysteresis for the ground-fault current:
Hysteresis
0 to 15% of the level value in steps of 1%
Default setting: 5 %