Parameters
4.7 Standard functions
SIMOCODE pro - Parameterize
224 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
DIP switches (DM-F Local)
Sensor input automatic start / monitored start
• Automatic start: The enabling circuits are switched to the
operative position as soon as the starting condition at sensor
inputs Y12, Y22, Y34 and terminal 1 have been fulfilled. The start
button connection terminal Y33 is not queried.
• Monitored start: The enabling circuits are switched to the
operative position, as soon as the starting condition at sensor
inputs Y12, Y22, Y34 and terminal 1 have been fulfilled and the
start button at terminal Y33 has subsequently been actuated
(start with the falling edge).
Cascading input automatic start / monitored start
• Automatic start: The enabling circuits are switched to the active
position as soon as the switch-on condition at cascading input 1
is satisfied, i.e. as soon as a static +24 V DC signal is present
(e.g. from T3).
• Monitored start: The enabling circuits are switched to the
operative position as soon as the starting condition at cascading
input 1 has been fulfilled, i.e. as soon as a static +24 V DC signal
is present (e.g. from T3), and the start button at terminal Y33 has
subsequently been actuated (start with the falling edge).
With / without startup testing After a power failure, startup testing requires that the sensors at Y12
and Y22 are actuated once by the system operator.
With automatic starting / without automatic starting
after power failure
The DM-F Local can be parameterized in such a way that the
enabling circuits automatically switch to the operative position after a
power failure, i.e. without actuation of the start button Y33.
Prerequisites:
• Y12, Y22 or the cascading input 1 are set to "monitored start."
• The starting condition at the sensor inputs and at the cascading
input has been fulfilled.
• Valid actuation of the start button prior to the power failure, i.e.
the enabling circuits were in the operative position.