Parameters
4.7 Standard functions
SIMOCODE pro - Parameterize
226 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
"Safety-related tripping" response
Here, you set the SIMOCODE pro response to safety-related tripping via DM-F Local or
DM-F PROFIsafe.
Note
The response of the modules is not influenced by this setting
. If the conditions for safety-
related disconnection are met, the enable circuits are always disabled!
Table 4- 81 "Safety-related tripping" response
Response
Safety-related tripping
tripping
X
disabled
X (d)
signaling
X
warn
X
Note
In the event that the option "DM
-F LOCAL / Separate PROFIsafe function from control
function" has been activated under "Motor control
> Control function
> Operating mode," only
"disabled," "signal," or "warn" can be set as the
response, not "tripping."
"Safety-related tripping" reset
Here, you can select manual or automatic acknowledgment of SIMOCODE pro faults caused
by safety-related tripping.
Reset:
Manual (default), Auto