Blocksize Power Modules (PM240-2)
4.6 Technical data
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
103
Table 4- 24 Technical data of the PM240-2, FSC (400 V)
Line voltage 3-phase 380 … 480 V AC ± 10%
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE22-7UL0
1PE22-7AL0
6SL3210–
1PE23-3UL0
1PE23-3AL0
6SL3211–
1PE23-3UL0
1PE23-3AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
26.0
18.0
28.6
32.0
26.0
37.1
32.0
26.0
37.1
1)
on basis of I
n
kW
11.0
15.0
15.0
Rated pulse frequency
Max. Pulse frequency
kHz
4
4
4
4)
Sound pressure level LpA (1 m)
2)
of the external
Ω ≥ 30 ≥ 30 ≥ 30
Max. Cable length
to the braking resistor
L1, L2, L3,
Screw-type terminals
Cross head M4
Conductor cross section: 6 … 16 mm
2
Tightening torque: 1.3 Nm
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
3)
IP20 in the cabinet: IP20
Without line filter
kg
4.7
4.8
5.8
Rated output of a typical standard induction motor at 400 V.
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 50 m
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter class B and a motor reactor.
4)
Power loss in the cabinet: 0.075 kW. The remaining power loss is dissipated through the heat sink.