Blocksize Power Modules (PM240-2)
4.6 Technical data
SINAMICS S110
104 Manual, 07/2015, 6SL3097-4AC10-0BP5
Table 4- 25 Technical data of the PM240-2, FSD (400 V)
Line voltage 3-phase 380 … 480 V AC -20/+10 %
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE23-8UL0
1PE23-8AL0
6SL3210–
1PE24-5UL0
1PE24-5AL0
6SL3210–
1PE26-0UL0
1PE26-0AL0
6SL3210–
1PE27-5UL0
1PE27-5AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
38
32
45
45
38
54
60
45
72
75
60
90
1)
on basis of I
n
kW
18.5
22
30
37
Rated pulse frequency
Max. Pulse frequency
kHz 4
4
4
4
2)
of the external braking
Ω ≥ 27 ≥ 27 ≥ 15 ≥ 15
Max. Cable length
to the braking resistor
Line supply connection L1, L2, L3, PE
Screw-type terminal
Torx M5
Conductor cross section: 16 … 35 mm
2
Tightening torque: 2.5 … 4.5 Nm
Motor connection U2, V2, W2, PE
DCP, DCN
Connection for braking resistor
R1, R2 Screw-type terminal
Torx M4
Conductor cross section. 2.5 … 16 mm
2
Tightening torque: 1.2 … 1.5 m
3)
Without line filter
kg
16
16
17
17
Rated output of a typical standard induction motor at 400 V.
The input current depends
on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 150 m
(shielded) it the max. motor cable length.